| 09/12/2008 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 09/10/2008 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. PROVIDE PRIMER & TAPE ON ALL UNDERGROUND FITTING AND TOOL MARKS 2. PROVIDE APPROVED COVER ON ALL UNDERGROUND GAS PIPING 3. COMPLETE LIST AND CALL BACK FOR FINAL |
|
| 09/05/2008 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. PROVIDE A GAUGE WITH 1/10 PSI INCREMENTATION MIN. OF 10 PSI 2. PROVIDE PRESSURE TEST ON ALL GAS PIPING 3. COVER ALL UNDERGROUND FITTING AND TOOL MARKS WITH TAPE & PRIMER 4. PROVIDE APPROVED COUPLINGS NOT THREAD PROTECTORS 5. EXTEND FLUE VENT ON ROOF 2' ABOVE COOL WITH DOUBLE WALK 6. PROVIDE NEW AGA APPROVED VALVE FOR WATER HEATER |
|
| 09/03/2008 | PLUMBING - FINAL | Cancelled | CANCELLED PER HOMEOWNER AURRORA YBARRA #294-1772 | |
| 09/03/2008 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELED |