Permit: T08PL01281

Parcel: 104071550


Addresses:

4110 N LANGE AV

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
09/02/2008 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
08/29/2008 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
PROVIDE A SHUT OFF VALVE AT HOUSE
INSTALL SCOTCH-KOTE PIPING AT HOUSE, FIELD WRAPPING BLACK STEEL IS NOT ACCEPTABLE.
COMPLETE WH VENT
B VENT IN UPSIDE DOWN
PROVIDE A PERMIT FOR NEW FURNACE
EXTEND FURNACE VENT TERMINATION TO 3' ABOVE SWAMP COOLER. INSTALL 3X4 INCREASER AS CLOSE TO FURNACE AS POSSIBLE.