Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/26/2008 | PLUMBING - FINAL | Approved | IVRS - Inspection :* GAS CARD @ METER SW GAS 889-1888 |
|
| 08/13/2008 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GAUGE READING 7.5 PSI 2. MIN. 10 PSI REQUIRED AND CODES REQUIRE A GAUGE WITH 1/10TH PSI INCREMENTATIONS. 3. PROVIDE CORRECT GAUGE AND 10 PSI TEST 4. WH OK 5. OK TO COVER YARD LINE IF HOLDING TEST |
|
| 08/12/2008 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. WRAP ALL TOOL MARKS BELOW GRADE 2. TEST ENTIRE SYSTEM 3. COMPLETE PIPING TO NEW FAV. 3/4" REQ. 4. PROVIDE A PERMIT FOR NEW FAV. PERRY HEATING & COOLING 5. CORRECT WH VENT AND T&P DRAIN AT UNINSPECTED WATER HEATER |