Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/21/2008 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 08/18/2008 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. PROVIDE CITY APPROVED GAS ISOMETRIC IF FUTURE GAS IS NEEDED FOR ROOFTOP UNIT OR REMOVE TEES FOR FUTURE ROOFTOP UNIT AND OTHER FUTURE TEE ON ROOF 2. EXTEND GAS PIPE INTO WATER HEATER ENCLOSURE WITH RIDGID PIPE NIPPLE 3. INSTALL DRAFT HOOD PROPERLY AND VENT PIPING FOR WATER HEATER IN CORRECT DIRECTION OF FLOW 4. SEAL GAS PIPING INTO BUILDING 5. PROVIDE BONDING OF GAS SYSTEM 6. PLEASE FIND LISTING ON PIPE AND SHOW US ITS LISTING 7. PROVIDE PIPE PROTECTION PLATES AS REQUIRED LUIS 977-8339 |
|
| 08/14/2008 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* NO ACCESS AT 9:08 PROVIDE ACCESS AT NEXT INSPECTION |
|
| 08/13/2008 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* |