Inspection History Details
Inspection Status: Partial Approval
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/31/2008 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* 1. CORRECT AND RECALL FOR FINAL APPROVAL 2. SECURE B VENT TO DRAFT COLLAR W/3 GALV SHEETMETAL SCREWS 3. PROVIDE APPROVED B-VENT BRACKET AT EVE 4. INSTALL A SEDIMENT TRAP THIS IS A NEW APPLIANCE 5. PROVIDE APPROVED MATERIAL FOR T&P DRAIN 6. PIPE CLAMPS ARE PREFERRED RATHER THAN CONDUIT CLAMPS 7. WATER HEATERS INSTALLED OUTSIDE REQUIRE PROTECTION FROM THE ELEMENTS 8. WATER PIPING REQUIRES PROPER SUPPORT 9. CONDUIT CLAMPS ARE FERROUS METAL AND MAY NOT CONTACT COPPER |