Date Description Inspector Results Comments
11/13/2008 PLUMBING - FINAL Approved IVRS - Inspection :*
GAS PIPING TO STOVE AND WATER HEATER ONLY
10/30/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. UNCOVER ALL UNDERGROUND GAS PIPING
2. PROVIDE APPROVED SUPPORT ON GAS PIPING
3. PROVIDE DOUBLE WALL FLUE CAP AT WATER HEATER
4. PROVIDE PRIMER & TAPE ON ALL UNDERGROUND
GAS PIPING
5. RUN T&P FROM WATER HEATER TO DAYLIGHT
6. PROVIDE MIN. 10 PSI TEST ON ALL GAS PIPING