Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
07/23/2008 PLUMBING - FINAL Approved IVRS - Inspection :*
GAS CARD @ METER
SW GAS 889-1888
07/21/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. TEST TO HOLD WITH NO LOSS OF PRESSURE
2. PROVIDE ROOF JACK AT METER LOCATION WHERE PIPE GOES THRU ROOF STRUCTURE MADE WEATHER TIGHT
07/18/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
TEST HOLD WITH NO LOSS OF PRESSURE

1. PROVIDE WEATHER TREATED SUPPORTS FOR ROOFTOP PIPING
2. PROVIDE FULL SIZE 3/4" APPROVED MATERIAL GRAVITY DRAIN TO DAYLIGHT TERMINATING 6" TO 24" WITH 90 DEG. DOWN FOR TEMPERATURE & PRESSURE RELIEF DRAIN PIPING
3. PROVIDE CSA OR AGA GAS VALVE FOR WATER HEATER WITH SEDIMENT TRAP AT GAS INLET
4. PROVIDE BONDING OF BUILDING GAS PIPING
5. PROVIDE SEDIMENT TRAP AT GAS ENTRY TO ROOFTOP UNIT