Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/09/2008 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 07/08/2008 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* FRONT HOUSE ONLY 1. PROVIDE A 10 PSI AIR TEST USING A GAUGE WITH 1/10TH PSI INCREMENTATIONS (15PSI) 2. REMOVE THREAD PROTECTOR AND INSTALL A LISTED PIPE COUPLING 3. SECURE PIPING DROP AT WH NOTE WH INSTALLED W/OUT PERMIT 4. INSTALL SEDIMENT TRAP AT WH 5. CORRECT VENT 6. SECURE TO WH DRAFT COLLAR 7. PROPERLY TERMINATE T&P DRAIN |