Permit: T08PL00989

Parcel: 10820011B

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
09/26/2008 PLUMBING - FINAL Approved IVRS - Inspection :*
CORRECTIONS MADE OK
OWNER CAN REPLACE ENCLOSURE FRONT
09/24/2008 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
1. VENT CONNECTOR OUTSIDE ENCLOSURE BACKPITCHED
2. VENT CONNECTOR TO TERMINATE AT TOP OF ENCLOSURE AND THEN TRANSITION TO B-VENT
3. REMOVE TAPE BETWEEN B-VENT AND CONNECTOR
07/17/2008 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
VENT CONNECTOR HAS BACKPITCH
JOINTS ON SINGLE WALL VENT CONNECTORS ARE NOT PROPERLY MADE, ARE NOT SECURED AND TAPE IS NOT ALLOWED. PROVIDE 1" OF CLEARANCE AROUND B-VENT PASSING THROUGH EVE. GAS PIPING IS NOT PROPERLY SUPPORTED. GAS FLEXES MAY NOT BE REUSED. PROVIDE NEW GAS SUPPLY FLEXES. PLEASE MAKE ALL CORRECTIONS PRIOR TO NEXT INSPECTION. THE SAFETY OF YOUR TENANTS DEPENDS ON IT. COURTESY CALLS BEFORE AND AFTER PROVIDED. OWNER LIVES IN CALIFORNIA.
07/03/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
NO CHANGE FROM LAST INSPECTION
CONTINUED "NOT READY" WILL RESULT IN REINSPECTION FEE
06/27/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. A FLEX CONNECTOR MAY NOT PASS THROUGH A WALL OR PARTITION
2. SUPPORT PIPING ALONG WALL
3. REMOVE TAPE AT VENT JOINTS
CONNECTIONS TO BE MADE IN AN APPROVED MANNER