Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/26/2008 | PLUMBING - FINAL | Approved | IVRS - Inspection :* CORRECTIONS MADE OK OWNER CAN REPLACE ENCLOSURE FRONT |
|
| 09/24/2008 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* 1. VENT CONNECTOR OUTSIDE ENCLOSURE BACKPITCHED 2. VENT CONNECTOR TO TERMINATE AT TOP OF ENCLOSURE AND THEN TRANSITION TO B-VENT 3. REMOVE TAPE BETWEEN B-VENT AND CONNECTOR |
|
| 07/17/2008 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* VENT CONNECTOR HAS BACKPITCH JOINTS ON SINGLE WALL VENT CONNECTORS ARE NOT PROPERLY MADE, ARE NOT SECURED AND TAPE IS NOT ALLOWED. PROVIDE 1" OF CLEARANCE AROUND B-VENT PASSING THROUGH EVE. GAS PIPING IS NOT PROPERLY SUPPORTED. GAS FLEXES MAY NOT BE REUSED. PROVIDE NEW GAS SUPPLY FLEXES. PLEASE MAKE ALL CORRECTIONS PRIOR TO NEXT INSPECTION. THE SAFETY OF YOUR TENANTS DEPENDS ON IT. COURTESY CALLS BEFORE AND AFTER PROVIDED. OWNER LIVES IN CALIFORNIA. |
|
| 07/03/2008 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* NO CHANGE FROM LAST INSPECTION CONTINUED "NOT READY" WILL RESULT IN REINSPECTION FEE |
|
| 06/27/2008 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. A FLEX CONNECTOR MAY NOT PASS THROUGH A WALL OR PARTITION 2. SUPPORT PIPING ALONG WALL 3. REMOVE TAPE AT VENT JOINTS CONNECTIONS TO BE MADE IN AN APPROVED MANNER |