Inspection History Details
Inspection Status: Approved
Inspection History: SITE - SEWER
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/10/2008 | SITE - SEWER | Approved | IVRS - Inspection :* | |
| 11/03/2008 | SITE - SEWER | Partial Approval | IVRS - Inspection :* 1. BOB FROM RICK ENG. HAS TESTING DOCUMENTATION FOR MANHOLE #6 2. PIPING FROM MANHOLE #6 & #7 |
|
| 10/29/2008 | SITE - SEWER | Partial Approval | IVRS - Inspection :* 1. MANHOLES #5 TO #6 PIPING TEST OK 2. PAPERWORK FOR TESTING DONE BY BOB FROM RICK ENG. |
|
| 09/26/2008 | SITE - SEWER | Partial Approval | IVRS - Inspection :* 1. PER HIGHLIGHT ON PAGE C-302 2. PER HIGHLIGHT ON PAGE P-101 PROVIDE OK FROM PCDEQ BEFORE TIE-INS ON TO NEW SEWER |
|
| 09/24/2008 | SITE - SEWER | Partial Approval | IVRS - Inspection :* SDR35 - 14' OUTSIDE OF NORTHEAST SIDE OF NEW BUILDING |
|
| 09/22/2008 | SITE - SEWER | Partial Approval | IVRS - Inspection :* 1. MANHOLE VACUUM TESTING BOB FROM RICK ENG. ON SITE FOR TESTING. MANHOLE #3, #4, #5, #7, #2, #1 2. PIPING PSI FROM MANHOLE #3 TO #4 TO #5, TEST OK |
|
| 09/18/2008 | SITE - SEWER | Partial Approval | IVRS - Inspection :* | |
| 09/17/2008 | SITE - SEWER | Partial Approval | IVRS - Inspection :* C-302 PER HIGHLIGHT |
|
| 09/16/2008 | SITE - SEWER | Partial Approval | IVRS - Inspection :* PER HIGHLIGHT ON C-302 |
|
| 09/11/2008 | SITE - SEWER | Partial Approval | IVRS - Inspection :* | |
| 09/10/2008 | SITE - SEWER | Not ready for Inspection | IVRS - Inspection :* | |
| 09/08/2008 | SITE - SEWER | Partial Approval | IVRS - Inspection :* | |
| 09/04/2008 | SITE - SEWER | Not ready for Inspection | IVRS - Inspection :* | |
| 08/27/2008 | SITE - SEWER | Partial Approval | IVRS - Inspection :* SITE SEWER REPAIR HIGHLIGHT OF PAGE C-302 FROM CLAY TO DIP |
|
| 08/26/2008 | SITE - SEWER | Not ready for Inspection | IVRS - Inspection :* CANCELED |
|
| 08/12/2008 | SITE - SEWER | Partial Approval | IVRS - Inspection :* C-302 PAGE HIGHLIGHT FOR SITE SEWER |
|
| 08/11/2008 | SITE - SEWER | Not ready for Inspection | IVRS - Inspection :* | |
| 08/05/2008 | SITE - SEWER | Partial Approval | IVRS - Inspection :* 1. MANHOLE #1 TO #2 TEST OK 2. MANHOLE #2 TO #3 TEST OK 3. RICK (EWS) PAPERWORK IN ORDER FOR TESTING |
|
| 07/31/2008 | SITE - SEWER | Partial Approval | IVRS - Inspection :* MANHOLE #3 & #4 STACKED |
|
| 07/30/2008 | SITE - SEWER | Partial Approval | IVRS - Inspection :* MANHOLE BASE #3 & #4 POURED AND STACKING IN PROGRESS |
|
| 07/28/2008 | SITE - SEWER | Partial Approval | IVRS - Inspection :* 8" SDR FROM MANHOLE #2 TO #3 CONTINUES FROM MANHOLE #3 TO MANHOLE #4 AND STUBBED OUT OF MANHOLE #4 APP. 14' BEDDING, LAYING, SHADING, WITH TRACER OK - REVISED C-302 DATED 7/15/08 PCDEQ WILL REQUIRE CITY OF TUCSON APPROVAL SERVING AS REDLINE |
|
| 07/25/2008 | SITE - SEWER | Partial Approval | IVRS - Inspection :* PIPING TO MANHOLE #3 BEDDING, LAYING, TRACER, SHADING CONTINUES 28' TOWARD MANHOLE #4 |
|
| 07/24/2008 | SITE - SEWER | Partial Approval | IVRS - Inspection :* |