Permit: T08PL00894

Parcel: 118050010

Inspection Status: Approved

Inspection History: SITE - SEWER

Date Description Inspector Results Comments
12/10/2008 SITE - SEWER Approved IVRS - Inspection :*
11/03/2008 SITE - SEWER Partial Approval IVRS - Inspection :*
1. BOB FROM RICK ENG. HAS TESTING DOCUMENTATION FOR MANHOLE #6
2. PIPING FROM MANHOLE #6 & #7
10/29/2008 SITE - SEWER Partial Approval IVRS - Inspection :*
1. MANHOLES #5 TO #6 PIPING TEST OK
2. PAPERWORK FOR TESTING DONE BY BOB FROM RICK ENG.
09/26/2008 SITE - SEWER Partial Approval IVRS - Inspection :*
1. PER HIGHLIGHT ON PAGE C-302
2. PER HIGHLIGHT ON PAGE P-101 PROVIDE OK FROM PCDEQ BEFORE TIE-INS ON TO NEW SEWER
09/24/2008 SITE - SEWER Partial Approval IVRS - Inspection :*
SDR35 - 14' OUTSIDE OF NORTHEAST SIDE OF NEW BUILDING
09/22/2008 SITE - SEWER Partial Approval IVRS - Inspection :*
1. MANHOLE VACUUM TESTING BOB FROM RICK ENG.
ON SITE FOR TESTING. MANHOLE #3, #4, #5, #7, #2, #1
2. PIPING PSI FROM MANHOLE #3 TO #4 TO #5, TEST OK
09/18/2008 SITE - SEWER Partial Approval IVRS - Inspection :*
09/17/2008 SITE - SEWER Partial Approval IVRS - Inspection :*
C-302 PER HIGHLIGHT
09/16/2008 SITE - SEWER Partial Approval IVRS - Inspection :*
PER HIGHLIGHT ON C-302
09/11/2008 SITE - SEWER Partial Approval IVRS - Inspection :*
09/10/2008 SITE - SEWER Not ready for Inspection IVRS - Inspection :*
09/08/2008 SITE - SEWER Partial Approval IVRS - Inspection :*
09/04/2008 SITE - SEWER Not ready for Inspection IVRS - Inspection :*
08/27/2008 SITE - SEWER Partial Approval IVRS - Inspection :*
SITE SEWER REPAIR HIGHLIGHT OF PAGE C-302 FROM CLAY TO DIP
08/26/2008 SITE - SEWER Not ready for Inspection IVRS - Inspection :*
CANCELED
08/12/2008 SITE - SEWER Partial Approval IVRS - Inspection :*
C-302 PAGE HIGHLIGHT FOR SITE SEWER
08/11/2008 SITE - SEWER Not ready for Inspection IVRS - Inspection :*
08/05/2008 SITE - SEWER Partial Approval IVRS - Inspection :*
1. MANHOLE #1 TO #2 TEST OK
2. MANHOLE #2 TO #3 TEST OK
3. RICK (EWS) PAPERWORK IN ORDER FOR TESTING
07/31/2008 SITE - SEWER Partial Approval IVRS - Inspection :*
MANHOLE #3 & #4 STACKED
07/30/2008 SITE - SEWER Partial Approval IVRS - Inspection :*
MANHOLE BASE #3 & #4 POURED AND STACKING IN PROGRESS
07/28/2008 SITE - SEWER Partial Approval IVRS - Inspection :*
8" SDR FROM MANHOLE #2 TO #3 CONTINUES FROM
MANHOLE #3 TO MANHOLE #4 AND STUBBED OUT OF
MANHOLE #4 APP. 14' BEDDING, LAYING, SHADING, WITH TRACER OK - REVISED C-302 DATED 7/15/08 PCDEQ WILL REQUIRE CITY OF TUCSON APPROVAL SERVING AS REDLINE
07/25/2008 SITE - SEWER Partial Approval IVRS - Inspection :*
PIPING TO MANHOLE #3 BEDDING, LAYING, TRACER, SHADING
CONTINUES 28' TOWARD MANHOLE #4
07/24/2008 SITE - SEWER Partial Approval IVRS - Inspection :*