Permit: T08PL00887

Parcel: 135083040

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
06/09/2008 PLUMBING - FINAL Approved IVRS - Inspection :*
06/06/2008 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
ZIP TIE'S ARE NOT ACCEPTABLE TO HOLD INSULATED WATER TUBING AWAY FROM A WATER HEATER VENT THAT WILL NOT BE ACCESSIBLE. RE-WORK PIPING TO CREATE MINIMUM CLEARANCE REQUIRED.
06/05/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
NO ACCESS @ 9:30
PLEASE HAVE AN ADULT PRESENT TO PROVIDE ACCESS FOR REINSPECTION
06/03/2008 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. ADD WH TO PERMIT
2. SECURE HB
3. PIPE WH T&P DRAIN TO EXTERIOR
4. SECURE VENT CONNECTOR
5. PROVIDE CLEARANCE BETWEEN PEX AND WH VENT,
ALSO METAL
6. OK TO COVER EXCEPT AT WH