Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/11/2008 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 08/04/2008 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* UNPROTECTED HB ON EAST SIDE. VERIFY IF POTABLE AND CORRECT. IRRIGATION SYSTEM SUPPLIED BY WELL ANY HOSE BIBS ON IRR. SYSTEM SHALL BE REMOVED OR LABELED AS "CAUTION NON-POTABLE DO NOT DRINK" |
|
| 06/04/2008 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. OK TO COVER YARD WATER 2. NEED TO SEE APPROVED BACKFLOW PROTECTION ON ALL WATER OUTLETS INCLUDING IRRIGATION NOTE: WATER BEING USED BY CONSTRUCTION PERSONNEL FROM UNPROTECTED HOSE BIB MAY CONTAMINATE BUILDING WATER. INSTALL VAC BREAKERS ASAP |
|
| 06/03/2008 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* OK TO COVER PIPING IN ASPHALT EXPOSE ALL OTHER JOINTS INSTALL HB VAC BREAKER ON ALL HOSE BIBS TUC. WATER PERMIT REQUIRED FOR RP INSTALLATION |
|