Permit: T08PL00845

Parcel: 13314456A


Addresses:

1151 N EL DORADO PL

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
08/11/2008 PLUMBING - FINAL Approved IVRS - Inspection :*
08/04/2008 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
UNPROTECTED HB ON EAST SIDE. VERIFY IF POTABLE AND CORRECT. IRRIGATION SYSTEM SUPPLIED BY WELL
ANY HOSE BIBS ON IRR. SYSTEM SHALL BE REMOVED OR LABELED AS "CAUTION NON-POTABLE DO NOT DRINK"
06/04/2008 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. OK TO COVER YARD WATER
2. NEED TO SEE APPROVED BACKFLOW PROTECTION ON ALL WATER OUTLETS INCLUDING IRRIGATION

NOTE: WATER BEING USED BY CONSTRUCTION PERSONNEL FROM UNPROTECTED HOSE BIB MAY CONTAMINATE BUILDING WATER. INSTALL VAC BREAKERS ASAP
06/03/2008 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
OK TO COVER PIPING IN ASPHALT
EXPOSE ALL OTHER JOINTS
INSTALL HB VAC BREAKER ON ALL HOSE BIBS
TUC. WATER PERMIT REQUIRED FOR RP INSTALLATION
05/27/2008 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. EXPOSE CU TO PVC CONNECTIONS
2. REMOVE ALL ROCKS AND DEBRIS FROM TRENCH
3. INSTALL A BLUE TRACER WIRE AND SECURE TO PIPING
AT 8' O.C PER STATE LAW