Permit: T08PL00833

Parcel: 131091860


Addresses:

5626 E 26TH ST


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T08PL00833

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/27/2008 PLUMBING - FINAL Approved IVRS - Inspection :*
08/25/2008 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. TEST SYSTEM IN ITS ENTIRETY
(BLD. SHUT OFF VALVE IS OFF)
2. BUILDING SHUT OFF VALVE IS REQUIRED TO BE AGA OR CSA APPROVED GAS VALVE
3. BONDING AREA OF CLAMP TO BE CLEAN TO PROVIDE GOOD CONNECTION (IT IS PAINTED) AND WIRE TO BE #4 OR #6 WIRE
4. UNDERGROUND PIPING TO HAVE ALL TOOL MARKS PRIMED AND TAPED PER INSPECTION NOTE #3 5/28/08 INSPECTION HISTORY

NOTE: FOR YOUR BENEFIT WE HAVE LEFT CORRECTIONS PLEASE READ THEM AND COMPLY
08/04/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
PIPE NOT 12" DEEP
NO WALL PENETRATIONS SEALED
NO BOND - NO TEST
CONTRACTOR TO PAY REINSPECTION FEE
05/28/2008 PLUMBING - FINAL Partial Approval 1. PROVIDE WATER HEATER T&P DRAIN FULL SIZE GRAVITY DRAIN TO DAYLIGHT TERMINATING 90 DEG. DOWN 6"-24" FROM FINISH GRADE
2. SEAL ALL PIPE PENETRATIONS THRU BLD. WALL
3. PRIME THEN TAPE ALL TOOL MARKS ON UNDERGROUND PIPING
4. PROVIDE BONDING OF BLD. GAS PIPING
5. PIPE TAPE TO BE APPLIED PROPERLY, DOUBLE WRAPPED WITH 1/2 OVERLAY TO ACHIEVE 40 MIL. THICKNESS
PRIMED FIRST ALL TOOL MARKS & FITTING BELOW GRADE
6. HAVE PROPERLY SIZED RATED BTU FLEXES ON SITE
05/27/2008 PLUMBING - FINAL Cancelled CANCELLED PER BONNIE OF SILVERADO PLUMBING #696-0000
05/27/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
CONTRACTOR CANCELED