Permit: T08PL00833

Parcel: 131091860


Addresses:

5626 E 26TH ST


Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Permit Number - T08PL00833

Inspection Description - PLUMBING - GAS PRESSURE TEST

Inspection Status - Approved

Date Description Inspector Results Comments
08/27/2008 PLUMBING - GAS PRESSURE TEST Approved PLUMBER WILL CLEAN COLD WATER PIPE & INSTALL BONDING CLAMP TO BLD. COLD WATER PIPING
GAS CARD @ METER
06/02/2008 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
1. WILL REQUIRE AN APPROVED PLAN - THIS IS A COMMERCIAL PROJECT
2. GAS PIPING REQUIRES A MINIMUM OF 12" OF COVER AT ALL POINTS
3. SEAL EXTERIOR WALL PENETRATION
4. BOND GAS AND WATER PIPING

CONTINUED "NOT READY" WILL RESULT
IN A REINSPECTION FEE
05/28/2008 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
TEST HOLDING AT THIS TIME MAKE CORRECTIONS AND LEAVE TEST IN PLACE
05/27/2008 PLUMBING - GAS PRESSURE TEST Cancelled
05/27/2008 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
CONTRACTOR CANCELED