Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T08PL00832
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/23/2008 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
05/22/2008 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ALL ANGLE STOPS TO BE PROPERLY SECURED 2) SECURE TUB AND SHOWER VALVES PROPERLY 3) PROVIDE APPROVED MATERIAL FOR SUPPLIES TO FIXTURES 4) SECURE PIPING AT WATER HEATER AREA PROPERLY 5) PROVIDE MINIMUM 6" METALIC PIPING AT WATER HEATER SUPPLY IN AND OUT OF WATER HEATER 6) PROVIDE FULL SIZE 1" DISTRIBUTION FOR CORRECT SIZING ON COLD INLET PIPING 7) SECURE AND SUPPORT PIPING IN ATTIC PROPERLY 8) PROVIDE VACUUM BREAKERS AT ALL HOSE BIBS |