Permit: T08PL00752


Addresses:

9047 S RITA RD

Inspection Status: Approved

Inspection History: PLUMBING - YARD WTR LINE/TEST

Date Description Inspector Results Comments
08/01/2008 PLUMBING - YARD WTR LINE/TEST Approved IVRS - Inspection :*
TIE-IN's AT ALL BLDS & AREAS OK
07/30/2008 PLUMBING - YARD WTR LINE/TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
EXPOSE ALL JOINTS AT MAIN BLD, ALL RESTRAINT NUTS TO BE TORQUED PROPERLY. WATER SYSTEM TO BE ENERGIZED TO BOTH BLDS. FOR INSPECTION
07/18/2008 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
PIPING FROM METER THRU RPBS TIES INTO (2) 4" C-900 TO
5' FROM BLD.
06/09/2008 PLUMBING - YARD WTR LINE/TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
SADDLE INSTALL OK FOR 1"

1. SHALL PROVIDE PLASTIC MALE IRON PIPE X FEMALE I.P CONNECTION FOR TRANSITION AT CORP. STOP PROVIDE TEST ON PIPING
06/02/2008 PLUMBING - YARD WTR LINE/TEST Not ready for Inspection IVRS - Inspection :*
COMPLETE LISTS FROM OTHER INSPECTIONS
05/30/2008 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
INSTALL OF RESTRAINTS AT METER LOCATION ON (2) 4" C-900 OK
05/29/2008 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
1" PVC SCH 40 FROM (2) 4" C-900 AT METER AREA TO 30' FROM GUARD HOUSE

1. PROVIDE TRACER WIRE AND TEST ON PVC SCH 40 1" PIPE
2. PROVIDE RESTRAINTS ON (2) 4" C-900 AT METER LOCATION, AND PROVIDE INSPECTION ON TIE TOGETHER OF PIPING TO METER AND GUARD HOUSE LINE