Permit: T08PL00707

Parcel: 121092890

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T08PL00707

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/12/2008 PLUMBING - FINAL Approved IVRS - Inspection :*
05/07/2008 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- CODE DOES NOT ALLOW PIPES TO BE SUPPORTED FROM OTHER PIPES
- THIN PLASTIC CABLE TIES ARE NOT MADE TO SUPPORT PIPING
- YOU SHALL USE LISTED PIPE SUPPORTS, SUCH AS ISOLATORS, BEAM CLAMPS, UNISTRUT, WOOD W/TWO HOLE STRAPS MADE FOR PEX
- HAS INSTALLER BEEN TRAINED AND CERTIFIED TO INSTALL PEX TUBING PER MANUFACTURERS REQUIREMENTS?

PROVIDE OWNER W/PEX INSTALLATION INSTRUCTIONS.
05/02/2008 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- ISOLATE CU TOUCHING METAL AT SERVICE
- SUPPORT PEX W/APPROVED PIPING SUPPORTS AT CORRECT INTERVALS PER PEX INSTALLATION INSTRUCTIONS
- SECURE TUBING SO THAT IT DOES NOT CONTACT METAL AND DOES NOT CAUSE WATER HAMMER
04/30/2008 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
PROVIDE HB VAC BREAKER ON HB
PROVIDE ACCESS TO INSPECT PIPING BELOW HOME