Permit: T08PL00706

Parcel: 124070730


Addresses:

702 E 9TH ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
05/13/2008 PLUMBING - FINAL Approved IVRS - Inspection :*
GAS CARD AT METER
04/30/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. PROVIDE 1" MINIMUM CLEARANCE FOR WATER HEATER VENT THRU ROOF AT STRUCTURE
2. PROVIDE UPPER COMBUSTION AIR FOR 75,000 BTU WATER HEATER
3. T&P WILL TERMINATE AT FLOOR DRAIN WITH
MIN. 1" AIR GAP