Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T08PL00703
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/01/2008 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
04/30/2008 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE PIPING CONFIGURATION SO WATER HEATER CAN BE REMOVED 2. SUPPORT PIPING IN FURNACE/WATER HEATER CLOSET 3. PROVIDE COMBUSTION AIR FOR COMBINED BTU REQUIREMENTS FOR WATER HEATER/FURNACE 4. REMOVE ALL TAPE FROM VENT PIPING & PROVIDE APPROVED FASTENERS FOR ALL JOINTS OF VENT PIPING ON FURNACE AND WATER HEATER 5. PROVIDE BONDING OF BUILDING GAS SYSTEM (NOT GROUNDING) |
|
04/29/2008 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE TEST OF MINIMUM 10 PSI AT TIME OF INSPECTION 2. NO ACCESS AT 8:40 -- LIST NOT COMPLETE |