Permit: T08PL00682

Parcel: 116182320


Addresses:

64 N PALOMAS AV

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
05/05/2008 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
05/01/2008 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
THIS INSPECTION IS FOR THE BACK GUESTHOUSE ONLY
PROVIDE FLASHINGS AT ROOF PENETRATIONS
SUPPORT PIPING W/TREATED OR REDWOOD SUPPORTS
PROPERLY ALIGN JOINTS AND SUPPORT PER UPC T 3-2
CORRECT WH VENT 5' MIN. B VENT
SECURE VENT W/GALV SHEETMETAL SCREWS
SECURE ENCLOSURE
04/28/2008 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
PROVIDE PRESSURE TEST ON ALL GAS PIPING MIN. 10 PSI
WITH GAUGE IN 1/10 PSI INCREMENTATION