Permit: T08PL00627

Parcel: 118080690

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
04/25/2008 PLUMBING - FINAL Approved IVRS - Inspection :*
04/18/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. PROVIDE APPROVED TEMPERATURE & PRESSURE RELIEF DRAIN PIPING TERMINATING 6"-24" FROM FINISH GRADE FOR WATER HEATER
2. PROVIDE APPROVED VENT PIPING, DOUBLE WALL THRU ROOF WITH 1" MINIMUM CLEARANCE FROM COMBUSTIBLES WITH APPROVED ROOF JACK AND VENT CAP
3. PROVIDE BONDING OF BUILDING GAS PIPING SYSTEM
4. PROVIDE SUPPORT FOR GAS PIPING IN WATER HEATER AREA
5. PROVIDE MINIMUM (1) UPPER COMBUSTION AIR OPENING FROM EXTERIOR OF WATER HEATER AREA TO EQUAL 1 SQ. INCHES FOR EVERY 2000 BTU DEMAND OF 30,000 BTU WATER HEATER