Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/17/2008 | PLUMBING - GAS PRESSURE TEST | Cancelled | CANCELLED PER ARCHITECT BOB TAYLOR #318-9989 | |
| 04/17/2008 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE MINIMUM 10 PSI TEST ON ENTIRE GAS SYSTEM AT TIME OF INSPECTION TO HOLD FOR 15 MINUTES WITH NO LOSS OF PRESSURE 2. REMOVE TAPE AT SINGLE TO DOUBLE WALL VENT CONNECTION OF WATER HEATER & PROVIDE AN APPROVED DOUBLE WALL VENT CAP 3. PROVIDE A PERMIT & HAVE FURNACE INSTALLED FOR FURNACE WITH APPROVED GAS VALVE AT THIS LOCATION LIST MAY NOT BE COMPLETE |