Permit: T08PL00527

Parcel: 130071180


Addresses:

3756 E JUAREZ ST

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
01/26/2009 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
01/22/2009 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. TEST TO BE ON ENTIRE GAS PIPING SYSTEM, WITH APPROVED GAS SHUT OFF VALVE AT SERVICE ENTRY TO STRUCTURE
2. PROVIDE RIDGID NIPPLE THRU ENCLOSURE OF WATER HEATER ON GAS PIPING
3. SEE NOTES FROM 4/15/08 ABOVE
4. PROVIDE AGA OR CSA APPROVED GAS SHUT OFF
VALVE AT STOVE