Inspection History: PLUMBING - FINAL
Permit Number - T08PL00494
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/01/2008 | PLUMBING - FINAL | Approved | IVRS - Inspection :* GAS CARD AT METER SW GAS 889-1888 |
|
03/31/2008 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. CONNECT THE YARD PIPING TO HOUSE PIPING TURN ON VALVE AT BUILDING ENTRY AND TEST THE ENTIRE GAS SYSTEM AS REQUESTED ON 3/26/08 REMOVE THE TAPE ON VENT PIPING FROM WATER HEATER 2. FURNACE AND SECURE JOINTS WITH SHEETMETAL SCREWS AS REQUESTED ON 3/26/08 3. HAVE NEW AGA OR CSA APPROVED APPLIANCE SHUT OFF VALVES AND FLEXES ON SITE FOR ALL APPLIANCES. |
|
03/26/2008 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - YARD PIPING OK - CONNECT TO HOUSE AND TEST ENTIRE SYSTEM - INSTALL AN EXTERIOR SOV AT HOUSE - PROVIDE ELECTRICAL BONDING - CORRECT SLOPE ON WH T&P DRAIN - REMOVE TAPE AT B VENT CONNECTION AND SECURE W/SHEETMETAL SCREWS - EXTEND B VENT TERMINATION TO 3' ABV COOLER |