Permit: T08PL00479

Parcel: 136250600


Addresses:

6624 E 39TH ST

Inspection Status: Partial Approval

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
03/25/2008 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
- CORRECT VENT CONNECTOR CONNECTION TO B VENT AT WH
- PLUMB AND SECURE W/3 SCREWS AT EACH JOINT
AND NO TAPE
- RECALL FOR INSP.
- CLEARANCE GIVEN
03/21/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
- THREADS ON 1" PIPE ARE NOT IN COMPLIANCE W/TABLE 12-2 UPC PAGE 154
- THREADS SHALL BE VISIBLE BEYOND FITTINGS NOT BOTTOMED OUT
- PROVIDE A 10 PSI TEST WITH A 15 PSI GAUGE
- PROVIDE ELECTRICAL BONDING
- COMPLETE VENTING. SECURE ALL JOINTS W/GALV SHEETMETAL SCREWS
- PIPE WH T&P TO APPROVED LOCATION OR PROVIDE PETITION OF APPEAL W/BUILDING OFFICIAL SIGNATURE
- SEDIMENT TRAPS REQUIRED AT FURN/WH LOCATION
- INSTALL HOUSE SERVICE VALVE UPSTREAM OF UNION
- OK TO COVER PE