Inspection Status: Partial Approval
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/25/2008 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* - CORRECT VENT CONNECTOR CONNECTION TO B VENT AT WH - PLUMB AND SECURE W/3 SCREWS AT EACH JOINT AND NO TAPE - RECALL FOR INSP. - CLEARANCE GIVEN |
|
| 03/21/2008 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* - THREADS ON 1" PIPE ARE NOT IN COMPLIANCE W/TABLE 12-2 UPC PAGE 154 - THREADS SHALL BE VISIBLE BEYOND FITTINGS NOT BOTTOMED OUT - PROVIDE A 10 PSI TEST WITH A 15 PSI GAUGE - PROVIDE ELECTRICAL BONDING - COMPLETE VENTING. SECURE ALL JOINTS W/GALV SHEETMETAL SCREWS - PIPE WH T&P TO APPROVED LOCATION OR PROVIDE PETITION OF APPEAL W/BUILDING OFFICIAL SIGNATURE - SEDIMENT TRAPS REQUIRED AT FURN/WH LOCATION - INSTALL HOUSE SERVICE VALVE UPSTREAM OF UNION - OK TO COVER PE |