Inspection History Details
Inspection Status: Approved
Inspection History: SITE - SEWER
Permit Number - T08PL00460
Inspection Description - SITE - SEWER
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/15/2009 | SITE - SEWER | Approved | IVRS - Inspection :* | |
| 10/20/2008 | SITE - SEWER | Partial Approval | IVRS - Inspection :* MANHOLE VACUUM TESTING #1 OK #2 OK #3 OK #4 OK #5 OK NEED TO SEE WATERPROOF FRAME & COVER PER DETAIL 213.2 FOR MANHOLE #4 AND AUTHORIZATION TO DISCHARGE PCDEQ |
|
| 10/16/2008 | SITE - SEWER | Partial Approval | IVRS - Inspection :* AIR TESTING - MANHOLE #1 TO #2 OK --- 8" SDR PIPING #2 TO #3 OK #3 TO #4 OK INCLUDING 4" HCS #4 TO #5 OK #5 TO EXISTING OK |
|
| 10/03/2008 | SITE - SEWER | Partial Approval | IVRS - Inspection :* - PIPING BETWEEN MH #1 AND #2 OK - MH BASES #1 & #2 BEING WORKED ON WILL REINSPECT AT TEST TIME - SCHEDULE TEST TIME ONE DAY IN ADVANCE |
|
| 10/02/2008 | SITE - SEWER | Partial Approval | IVRS - Inspection :* PIPING BETWEEN #3 & 2 OK MH BASES 3 & 4 OK |
|
| 09/29/2008 | SITE - SEWER | Partial Approval | PIPING BETWEEN 3 & 4 OK | |
| 09/24/2008 | SITE - SEWER | Partial Approval | IVRS - Inspection :* 1. PIPING BETWEEN #4 AND #5 APPEARS TO HAVE A SLIGHT CURVE. CHECK ALIGNMENT. OK TO COVER AFTER THIRD PARTY INSPECTION AND VERIFICATION |
|
| 09/22/2008 | SITE - SEWER | Partial Approval | IVRS - Inspection :* FROM EXISTING MH TO NEW MANHOLE #5 PIPING OK VERIFY GRADE WILL AIR TEST LATER |