Permit: T08PL00412

Parcel: 133210600

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
03/11/2008 PLUMBING - FINAL Approved IVRS - Inspection :*
3 SCREWS IN EACH JOINT
03/10/2008 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
FURNACE VENT MUST CONNECT TO BOTTOM OF TEE AND WH INTO SIDE
INSTALL B VENT IN CORRECT DIRECTION OF FLOW
PROVIDE PRESSURE TEST
03/07/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
TEST W/15 PSI GAUGE
COMPLETE VENTING FOR WH AND FURNACE
FURNACE REQUIRES 4" VENT
SINGLE WALL REQUIRES 6" CLEARANCE
NEW FURNACE REQUIRES A PERMIT
SEDIMENT TRAPS REQUIRED AT NEW WH & FURNACE
BOND W/#5 GROUNDING WIRE
FLEX NOT ALLOWED ON T&P
PVC NOT APPROVED FOR T&P DISCHARGE