Permit: T08PL00339

Parcel: 131043300


Addresses:

4826 E 27TH ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
03/05/2008 PLUMBING - FINAL Approved IVRS - Inspection :*
AFTER HRS. CHK#252 -- $150.00
GAS CARD AT METER
03/04/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
REMOVE ALL TAPE FROM VENT PIPING FOR
WATER HEATER & FURNACE AND COMPLY WITH NOTE #5
FROM 2/25/08 INSPECTION. ALL VENT PIPING TO BE IN GOOD FUNCTIONAL CONDITION.
02/25/2008 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. YOUR PLAN SHOWS ONLY A WATER HEATER AND FURNACE YOU HAVE THESE AND A DRYER & STOVE. YOUR GAS SYSTEM IS UNDERSIZED
2. PROVIDE CORRECT SIZED PIPING, EXPOSE ALL EXTERIOR PIPING FOR INSPECTION
3. SUPPORT ALL INTERIOR PIPING PROPERLY
4. PROVIDE RIDGID APPROVED WATER HEATER TEMPERATURE AND PRESSURE RELIEF DRAIN PIPING (NO FLEX)
5. PROVIDE CORRECT VENT CONNECTION FOR WATER HEATER TO FURNACE VENT WITH 3-GALV SCREWS AT ALL JOINTS WITH DRAFT HOOD INSTALLED CORRECTLY
6. TEST MUST HOLD MINIMUM 10 PSI WITH NO LOSS OF PRESSURE FOR 15 MINUTES. PROVIDE A WORKING TEST GAUGE IN 1/10TH POUND INCREMENTS
7. PROVIDE AN APPROVED GAS SHUT OFF VALVE AT EXTERIOR BUILDING ENTRY FOR EMERGENCY USE.