Inspection Status: Denied
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/27/2008 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SYSTEM TO BE TESTED IN ITS ENTIRETY, PROVIDE EMERGENCY GAS SHUT OFF VALVE AT CONNECTION TO BUILDING AND TEST TO ALL APPLIANCES. 2. YOUR WATER HEATER & FURNACE HAVE BEEN MOVED TO NEW LOCATIONS PROVIDE PLAN & PERMIT FOR THIS WORK AND ALL NEW WORK PROVIDE PERMIT FOR NEW WATER AND ROOFTOP UNIT OR PROOF OF INSPECTION OF THESE NEW APPLIANCES. PROVIDE PERMIT FOR NEW ELECTRICAL WORK OR PROOF OF INSPECTION. 3. COMPLETE PIPING TO ALL APPLIANCES & HAVE AGA OR CSA APPROVED GAS SHUT OFF VALVES & FLEXES 4. PROVIDE RIDGID NIPPLE THRU FURNACE APPLIANCE HOUSING 5. YOUR GAS SYSTEM APPEARS TO BE 160,000 BTU DEMAND PROVIDE A CITY APPROVED GAS ISOMETRIC OF THIS GAS SYSTEM IT IS INSTALLED UNDER SIZED FOR THE DISTANCE AND PIPE SIZE YOU HAVE INSTALLED LIST MAY NOT BE COMPLETE |