Permit: T08PL00312

Parcel: 136340260


Addresses:

7540 E MARY DR

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
02/21/2008 PLUMBING - FINAL Approved IVRS - Inspection :*
SW GAS 889-1888
02/20/2008 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. TEST TO HOLD WITH NO LOSS OR PRESSURE
2. WATER HEATER VENT TO TRAVEL IN UPHILL DIRECTION TO POINT OF TERMINATION AND BE SCREWED TOGETHER AT JOINTS.
3. WATER HEATER TEMPERATURE & PRESSURE RELIEF TO GRAVITY DRAIN TO DAYLIGHT. GO DOWN HILL.
4. WATER HEATER VENT TO BE EXTENDED TO 3' ABOVE TOP OF COOLER INTAKE WHEN WITHIN 10' WITH DOUBLE WALL VENT PIPING.
02/19/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. EXPOSE THE AREA THAT WAS REPAIRED FOR INSPECTION
BE SURE IT IS PROPERLY PRIMED THEN TAPED AT ALL TOOL MARKS AND FITTINGS BELOW GROUND TO 6" ABOVE GROUND.
2. TEST TO BE IN PLACE ON ENTIRE GAS SYSTEM
MINIMUM 10 PSI WITH NO LOSS FOR 15 MINUTES
3. NEED ACCESS TO ENTIRE GAS SYSTEM FOR INSPECTION
LIST MAY NOT BE COMPLETE