Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/06/2008 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 02/27/2008 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* RELIEF VALVE NOT RATED FOR 332500 BTU HEATER IN PUT ALSO, NOT PROPERLY TERMINATED |
|
| 02/22/2008 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* - 8 PSI TEST IS OK - OK TO BACKFILL TRENCH - PLEASE PROVIDE INSTALL INSTRUCTIONS - I DON'T SEE A TEMPERATURE & PRESSURE RELIEF VALVE INSTALLED |