Permit: T08PL00258

Parcel: 10606035A


Addresses:

926 W PRINCE RD


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T08PL00258

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/08/2008 PLUMBING - FINAL Approved IVRS - Inspection :*
1. CORRECTIONS MADE OK
2. OK FOR GAS
UCC LEFT AT METER

SW GAS 889-1888
02/07/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. UNDERGROUND PIPING TO BE SCOTCHCOAT
TAPING IS LIMITED TO FITTINGS AND MARRED PIPE
2. UNDERGROUND PIPING TO BE A MINIMUM OF 12" DEEP
3. PIPING TO BE SUPPORTED 3 1/2" ABOVE ROOF
4. ROOFTOP UNIT REQUIRED SEDIMENT TRAP
5. CHANGES OF DIRECTION TO BE MADE WITH APPROPRIATE FITTINGS