Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T08PL00246

Parcel: 127030030


Addresses:

1060 N CRAYCROFT RD

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
03/19/2008 PLUMBING - FINAL Approved IVRS - Inspection :*
MINOR REPAIRS ONLY ON EXISTING GAS SYSTEM ONLY
GAS CARD AT METER
03/12/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. TEST SYSTEM IN ITS ENTIRETY, ALL IN LINE VALVES TO BE OPEN, ANSUL VALVES TO BE OPEN TEST TO APPLIANCE SHUT OFF VALVES.
2. ALL UNUSED LOCATIONS TO BE PLUGGED OR CAPPED
3. ALL APPLIANCES TO HAVE CORRECT FLEXES (WHEELED APPLIANCES TO HAVE SAFETY CABLES INSTALLED & QUICK DISCONNECT FLEXES)
4. SUPPORT PIPING AT CORRECT INTERVALS AND AT CHANGES OF DIRECTION
02/21/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
POST YOUR ADDRESS
UNABLE TO LOCATE 1060 N