Permit: T08PL00228

Parcel: 126132980


Addresses:

4635 E MONTECITO ST


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T08PL00228

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/12/2008 PLUMBING - FINAL Approved IVRS - Inspection :*
GAS CARD AT METER
SW GAS 889-1888
02/11/2008 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
READ & COMPLY WITH ALL NOTES FROM 2/8/08 INSPECTION

NOTE: WATER HEATER VENT IS REQUIRED TO TERMINATE MINIMUM 3' ABOVE TOP OF COOLER INTAKE WHEN WITHIN 10' OF INTAKE. SUPPORT ALL PIPING PROPERLY.
02/08/2008 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. VENT FOR WATER HEATER TO BE INSTALLED IN CORRECT DIRECTION OF FLOW
2. SUPPORT GAS PIPING AT CORRECT INTERVALS AND AT CHANGES OF DIRECTION
3. PROVIDE SEDIMENT TRAPS AT GAS ENTRY TO WATER HEATER AND FURNACE
4. PROVIDE BONDING OF BUILDING GAS PIPING
5. GAS PIPING TO HOLD TEST FOR 15 MINUTES WITH NO LOSS OF PRESSURE
6. PROVIDE AGA OR CSA APPROVED GAS VALVES FOR ALL APPLIANCES
7. GAS PIPING SYSTEM IS UNDERSIZED FOR BTU DEMAND AND DISTANCE OF PIPING RUNS.