Permit: T08PL00188

Parcel: 130112950


Addresses:

2101 S MARCH PL

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
02/02/2008 PLUMBING - FINAL Approved IVRS - Inspection :*
02/01/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
01/31/2008 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- NEW HB REQUIRES VACUUM BREAKER
- RELIEF VALVE TERMINATION IS 6" ABOVE GRADE
- P OF A #419 08
- COMPLETE WORK AT WH, SECURE VENT
- 3/4" PIPE IS NOT ADEQUATE FOR 170,000 BTU
- A CITY APPROVED PLAN WOULD HAVE PREVENTED THIS MISTAKE. CORRECT SIZE. 1ST TEE WILL BE 1 X 3/4 X 3/4
- OK TO COVER PE
- PRESSURE TEST W/A 15 PSI GAUGE
- INSTALL EMERGENCY SOV AT BUILDING
- OK TO COVER PE YARD PIPING