Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/02/2008 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 02/01/2008 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 01/31/2008 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - NEW HB REQUIRES VACUUM BREAKER - RELIEF VALVE TERMINATION IS 6" ABOVE GRADE - P OF A #419 08 - COMPLETE WORK AT WH, SECURE VENT - 3/4" PIPE IS NOT ADEQUATE FOR 170,000 BTU - A CITY APPROVED PLAN WOULD HAVE PREVENTED THIS MISTAKE. CORRECT SIZE. 1ST TEE WILL BE 1 X 3/4 X 3/4 - OK TO COVER PE - PRESSURE TEST W/A 15 PSI GAUGE - INSTALL EMERGENCY SOV AT BUILDING - OK TO COVER PE YARD PIPING |