Permit: T08PL00176

Parcel: 130191260


Addresses:

4631 E 31ST ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
02/04/2008 PLUMBING - FINAL Approved IVRS - Inspection :*
1) GAS CARD AT METER
01/31/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. VENT FROM WATER HEATER & FURNACE TO BE EXTENDED WITH DOUBLE WALL FULL SIZE VENT PIPING 3' ABOVE TOP OF COOLER INTAKE WHEN WITHIN 10' OF INTAKE
2. SUPPORT GAS PIPING IN WATER HEATER/FURNACE CLOSET (DRIP LEG CANNOT BE THE SUPPORT OR TOUCH THE GROUND)
3. SECURE & SUPPORT GAS PIPING TO STOVE
4. REMOVE FUTURE TEE CONNECTION AT BUILDING AND AT METER OR HAVE THEM ADDED TO APPROVED PLAN.
RETEST SYSTEM.
5. PROVIDE AN AGA OR CSA APPROVED GAS VALVE AT FURNACE