Permit: T08PL00157


Addresses:

1631 N SWAN RD

Inspection Status: Partial Approval

Inspection History: SITE - SEWER

Date Description Inspector Results Comments
11/10/2008 SITE - SEWER Partial Approval IVRS - Inspection :*
CORRECTION OK
11/05/2008 SITE - SEWER Partial Approval IVRS - Inspection :*
MARTIN W/BAKER & ASSOC. PRESENT FOR TESTING.

VACUUM TESTING COMPLETE
PRESSURE TESTING OK, EXCEPT FOR RETEST REQUIRED AT CORRECTION BETWEEN #2 AND #6. RECALL FOR INSPECTION AND PROVIDE PCDEQ AUTHORIZATION TO DISCHARGE FOR FINAL APPROVAL.
10/30/2008 SITE - SEWER Not ready for Inspection IVRS - Inspection :*
CHIN-CHIN (909-3381)
10/23/2008 SITE - SEWER Partial Approval IVRS - Inspection :*
MET WITH CONTRACTOR WENT OVER TESTING
10/09/2008 SITE - SEWER Partial Approval IVRS - Inspection :*
1) DUCTILE IRON BETWEEN MHS 4 AND 5 OK
2) DUCTILE IRON BETWEEN MHS 3 AND 4 OK
3) NOTE: TAPING THE SIDE OF A PIPE IS NOT ACCEPTABLE. TAPE MUST BE AT A 45 DEGREE ANGLE
10/08/2008 SITE - SEWER Partial Approval IVRS - Inspection :*
- FROM MANHOLE #6 TO #7 WITH 20'4" HCS TOWARD LOT #11 FROM MANHOLE #7
- FROM MANHOLE #3 8" SP-2000 DUCTILE IRON APP. 140'

PLEASE NOTE DETAIL #3 SHEET 3 OF 3
10/07/2008 SITE - SEWER Partial Approval IVRS - Inspection :*
USE IVR SYSTEM TO SCHEDULE INSPECTIONS

FROM MH#1 TO #2, FROM #2 TO #3 AND FROM #2 TO #6 OK
WILL TEST LATER, AFTER TAPPING AND INSTALLING HCS CONNECTIONS. OK TO COVER AFTER 3RD PARTY VERIFICATION OF GRADE AND ENGINEER INSPECTION.