Permit: T08PL00155

Parcel: 11304148A

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
02/11/2008 PLUMBING - FINAL Approved IVRS - Inspection :*
1. CORRECTIONS MADE OK
NORMALLY THE PIPE STRAPS ARE THE SAME SIZE AS THE PIPE
I WILL ACCEPT OVERSIZE STRAPS THIS TIME ONLY.
FOR FUTURE REFERENCE, THE PIPING IS TO BE
SUPPORTED 3 1/2" ABOVE THE ROOF
2. PRESSURE TEST OK
3. OK FOR GAS
UCC LEFT AT METER

CONDENSATE DRAINS NEED TO BE RE-RUN AT STARTUP
02/08/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
SUPPORT VERTICAL PIPING ON WALL
NO ACCESS TO ROOF
CALLED 888-0877 AND NOTIFIED I WAS ON MY WAY
CONTRACTOR TO PAY REINSPECTION FEE
01/29/2008 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
COURTESY UNSCHEDULED INSP. FOR DAVE 888-7200

CORRECT MISSING PIPE SUPPORTS, 10 MAX.
KEEP PIPING MIN. 1 1/2" ABOVE ROOF
CORRECT LEAK, TEST AT 10 PSI
REPLACE GREASE COCKS W/AGA VALVES
SCHEDULE INSP. THRU IVR
01/28/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
PROVIDE ACCESS TO ROOF
10.3 PSI ON GAUGE
I WILL COME BACK TODAY IF YOU CALL ME BY 3:00 P.M.
OTHERWISE, RECALL IN FOR INSPECTION