Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: PLUMBING - FINAL
Permit Number - T08PL00153
Inspection Description - PLUMBING - FINAL
Inspection Status - Not ready for Inspection
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/07/2008 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. EXTENDED FLUE VENT FOR WALL FURNACE 2' ABOVE COOLERS FOR ALL UNITS AND CALL BACK FOR FINAL |
|
| 02/01/2008 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GAS PRESSURE TEST NOT HOLDING 2) PAY REINSPECTION FEE AT 201 N. STONE 3) PER COMMENT FORM 1/30/08 #3 |
|
| 01/30/2008 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. PRESSURE TEST NOT HOLDING 2. FIND LEAKS BEFORE CALLING FOR INSPECTION 3. CONTINUED "NOT READY" WILL RESULT IN REINSPECTION FEE 4. LIST MAY NOT BE COMPLETE |
|
| 01/29/2008 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. PRESSURE TEST NOT HOLDING 2. PROVIDE INSPECTION IN ALL UNITS FEEDING GAS METER 3. LIST MAY NOT BE COMPLETE |
|
| 01/28/2008 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. PSI TEST NOT HOLDING 2. PROVIDE TAPE & PRIMER ON FITTING AND TOOL MARK UNDERGROUND 3. PROVIDE ADDRESS ON DOORS 4. REPAIR LEAK BEFORE CALLING FOR INSPECTION |