Permit: T08PL00141

Parcel: 126050390


Addresses:

4019 E 1ST ST

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
02/01/2008 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
01/30/2008 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
SYSTEM IS LEAKING. CORRECT. TEST AT 10 PSI.
SUPPORT PIPING NEAR FURNACE.
SECURE PIPING AT FURNACE SHUT OFF VALVE.
(TAR BLOCK TO ROOF OR SECURE TO STAND)
01/29/2008 PLUMBING - GAS PRESSURE TEST Denied 1. 1/2" PIPING IS UNDERSIZED FOR 125,000 BTU
FURNACE 3/4 MIN. PIPE REQUIRED
2. SUPPORT PIPING W/LISTED PIPE CLAMPS AND WEATHER RESISTANT PIPE SUPPORTS
1 GALV 2 HOLE CLAMPS AND REDWOOD
SUPPORT EACH SECTION OF PIPE CLOSE TO JOINTS AND NOT EXCEEDING 6'
3. PROVIDE ACCESS TO STOVE
01/24/2008 PLUMBING - GAS PRESSURE TEST Cancelled CANCELLED PER HOMEOWNER ANDY COLLINS #954-4942