Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/01/2008 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* | |
| 01/30/2008 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* SYSTEM IS LEAKING. CORRECT. TEST AT 10 PSI. SUPPORT PIPING NEAR FURNACE. SECURE PIPING AT FURNACE SHUT OFF VALVE. (TAR BLOCK TO ROOF OR SECURE TO STAND) |
|
| 01/29/2008 | PLUMBING - GAS PRESSURE TEST | Denied | 1. 1/2" PIPING IS UNDERSIZED FOR 125,000 BTU FURNACE 3/4 MIN. PIPE REQUIRED 2. SUPPORT PIPING W/LISTED PIPE CLAMPS AND WEATHER RESISTANT PIPE SUPPORTS 1 GALV 2 HOLE CLAMPS AND REDWOOD SUPPORT EACH SECTION OF PIPE CLOSE TO JOINTS AND NOT EXCEEDING 6' 3. PROVIDE ACCESS TO STOVE |
|
| 01/24/2008 | PLUMBING - GAS PRESSURE TEST | Cancelled | CANCELLED PER HOMEOWNER ANDY COLLINS #954-4942 |