Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/04/2008 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 01/31/2008 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* - PRIME/WRAP TOOL MARKS ON COATED TRANSITION FITTINGS - INSTALL SHUT OFF VALVES AT EACH BUILDING ENTRY BECAUSE OF REMOTE METER LOCATION - REMOVE ADHESIVE TAPE FROM PE - USE PLASTIC TIES TO SECURE WIRE - PROVIDE FULL SIZE TEES AT FUR AND WATER HEATER CONNECTIONS - SEAL WALL PENETRATIONS - RETEST |