Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
Permit Number - T08PL00058
Inspection Description - PLUMBING - GAS PRESSURE TEST
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/18/2008 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* | |
| 01/14/2008 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* - GAUGE READING 4 PSI. CHECK FOR LEAKS - TEST AT 10 PSI - USE PIPE WRAP PRIMER AND 10 MIL PVC TAPE TO WRAP FITTINGS AND TOOL MARKS BELOW GRADE - PROVIDE AN EMERGENCY SHUT OFF VALVE AT HOUSE - ADD "NEW WATER HEATER" TO PERMIT - CONNECT FLUE PIPING AND SECURE W/SCREWS AT EACH JOINT - REMOVE FLEX ON T&P - INSTALL SEDIMENT TRAP AT W.H - RAISE TYPE B VENTS TO 3' ABOVE COOLER - 3/4" PIPE AT 60-80 DEVELOPED LENGTH IS UNDERSIZED FOR STOVE, FURNACE AND WH - INSTALL 1" PIPING TO CONNECTION W/EXISTING PIPING AT HOME |