Permit: T08PL00058

Parcel: 116170530


Addresses:

1103 W ERIE ST


Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Permit Number - T08PL00058

Inspection Description - PLUMBING - GAS PRESSURE TEST

Inspection Status - Approved

Date Description Inspector Results Comments
01/18/2008 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
01/14/2008 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
- GAUGE READING 4 PSI. CHECK FOR LEAKS
- TEST AT 10 PSI
- USE PIPE WRAP PRIMER AND 10 MIL PVC TAPE TO WRAP FITTINGS AND TOOL MARKS BELOW GRADE
- PROVIDE AN EMERGENCY SHUT OFF VALVE AT HOUSE
- ADD "NEW WATER HEATER" TO PERMIT
- CONNECT FLUE PIPING AND SECURE W/SCREWS AT EACH JOINT
- REMOVE FLEX ON T&P
- INSTALL SEDIMENT TRAP AT W.H
- RAISE TYPE B VENTS TO 3' ABOVE COOLER
- 3/4" PIPE AT 60-80 DEVELOPED LENGTH IS UNDERSIZED FOR STOVE, FURNACE AND WH
- INSTALL 1" PIPING TO CONNECTION W/EXISTING PIPING AT HOME