Permit: T08OT02908

Parcel: 106060180


Addresses:

1290 W PRINCE RD


Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T08OT02908

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/24/2010 FIRE - FINAL Approved Approved 2/24/10
02/24/2009 FIRE - FINAL Denied Not approved 2/24/09.
1.) Provide a sign over main exit reading "DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED"
2.) Cover opening in ceiling next to sprinkler deflector in front area closet.
3.) Cover opening in ceiling in kids playroom closet.
4.) Provide thumb-turn lock for door (interior side) front office.
5.) Provide breaker blanks for elecrical panel.
6.) Lable door to electrical panel room "ELECTRICAL PANEL".
7.) Provide thumb-turn locks for doors (interior side) leading out from pool area.
8.) Replace escucheon, Ladies bathroom.
9.) Replace the EXIT sign that was removed from the pool area.
10.) Cover plate and breaker blanks in Janitorial Closet.
11.) Replace ceiling tile, massage room, ladies bath.
12.) Extension cords are for temporary use only.
13.) Unapproved adaptors are prohibited.