Permit: T08OT02852

Parcel: 12108001B

Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T08OT02852

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/27/2009 FIRE - FINAL Approved The 5 yr. check valve inspection report responsibility has been assumed by the property manager. A field notice will be issued to the property manager.
12/19/2008 FIRE - FINAL Denied 1.) Need to provide correct approved plans.
2.) Nedd annual sprinkler inspection report.
3.) Need 5yr. check valve inspection report.
4.) Repair emergency back-up light located in the hallway.