Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T08OT02814
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/13/2009 | FIRE - FINAL | Approved | ||
12/02/2008 | FIRE - FINAL | Denied | (Pool room area) 1.Remove screen door from exit door, all exit doors shall swing outward. Install illuminated exit sign over exit door. 2.Remove dead bolt lock from exit door, only panic hardware allowed on door. (Bar floor area) 1.Remove screen door from exit door, all exit doors shall swing outward. 2.Remove slide bolt padlocks from exit door, only panic hardware allowed on door. 3.Install approved panic hardware on exit door. Repair or replace exit signs, all signs shall be illuminated at all times. All wiring below 7 feet in height shall be protected or in conduit, wiring in shelving area behind bar. Cover plate needed on J-box in kitchen by shelving. Remove x-mas tree from building not allowed in a type "A" occ. building. Need up to date hood inspection done, this done every 6 months. |