Permit: T08OT02766

Parcel: 132166160


Addresses:

845 E OHIO ST #103


Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T08OT02766

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/26/2008 FIRE - FINAL Approved 12' FOOT HIGH MAX STORAGE, IF GOING OVER NEED PLANS AND PERMITS.
11/24/2008 FIRE - FINAL Denied Rear exits remove double cylinder keyed dead bolt locks from panic hardware doors or remove panic hardware from doors and install thumb latch dead bolt locks.
Gate out of rear exit lock only with approved thumb latch dead bolt lock.
Remove propane cabinet out of building install outside 10 feet away from any building openings and protect from vehicle damage.