Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T08OT02766
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/26/2008 | FIRE - FINAL | Approved | 12' FOOT HIGH MAX STORAGE, IF GOING OVER NEED PLANS AND PERMITS. | |
11/24/2008 | FIRE - FINAL | Denied | Rear exits remove double cylinder keyed dead bolt locks from panic hardware doors or remove panic hardware from doors and install thumb latch dead bolt locks. Gate out of rear exit lock only with approved thumb latch dead bolt lock. Remove propane cabinet out of building install outside 10 feet away from any building openings and protect from vehicle damage. |