Inspection History Details
Inspection Status: Approved
Inspection History: CERTIFICATE OF OCCUPANCY
Permit Number - T08OT02730
Inspection Description - CERTIFICATE OF OCCUPANCY
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/02/2009 | CERTIFICATE OF OCCUPANCY | Approved | IVRS - Inspection :* | |
11/19/2008 | CERTIFICATE OF OCCUPANCY | Not ready for Inspection | IVRS - Inspection :* 1. ADDRESS DISPLAY REQUIRED ON STORE FRONTAGE 2. PLAN DOES NOT SHOW CORRECT FIXTURE LAYOUT PROVIDE NEW FLOORPLAN FOR WHAT YOU ACTUALLY HAVE 3. REVERSE PRESSURE, BACKFLOW ASSEMBLY REQUIRED FOR SODA CARBONATOR 4. CAULK TOILET @ FLOOR & LAVATORY @ WALL 5. GROUNDING ELECTRODE SYSTEM TO BE VERIFIED BY LICENSED CONTRACTOR. GROUNDING ELECTRODE CONDUCTOR IS MISSING 6. HOSE BIBB BEHIND 3 COMPARTMENT SINK REQUIRES AN ANTI-SIPHON DEVICE 7. PROVIDE PERMIT & INSPECTION HISTORY FOR A/C UNIT INSTALLED IN 2005 8. PROPERLY SUPPORT CONDUIT CONTAINING AC CONDUCTORS |