Permit: T08OT02730

Parcel: 12613018A

Inspection Status: Approved

Inspection History: CERTIFICATE OF OCCUPANCY

Permit Number - T08OT02730

Inspection Description - CERTIFICATE OF OCCUPANCY

Inspection Status - Approved

Date Description Inspector Results Comments
02/02/2009 CERTIFICATE OF OCCUPANCY Approved IVRS - Inspection :*
11/19/2008 CERTIFICATE OF OCCUPANCY Not ready for Inspection IVRS - Inspection :*
1. ADDRESS DISPLAY REQUIRED ON STORE FRONTAGE
2. PLAN DOES NOT SHOW CORRECT FIXTURE LAYOUT PROVIDE NEW FLOORPLAN FOR WHAT YOU ACTUALLY HAVE
3. REVERSE PRESSURE, BACKFLOW ASSEMBLY REQUIRED FOR SODA CARBONATOR
4. CAULK TOILET @ FLOOR & LAVATORY @ WALL
5. GROUNDING ELECTRODE SYSTEM TO BE VERIFIED BY LICENSED CONTRACTOR. GROUNDING ELECTRODE CONDUCTOR IS MISSING
6. HOSE BIBB BEHIND 3 COMPARTMENT SINK
REQUIRES AN ANTI-SIPHON DEVICE
7. PROVIDE PERMIT & INSPECTION HISTORY FOR A/C UNIT INSTALLED IN 2005
8. PROPERLY SUPPORT CONDUIT CONTAINING AC CONDUCTORS