Permit: T08OT02712

Parcel: 12801005H

Inspection Status: Approved

Inspection History: SIGN SHOP

Permit Number - T08OT02712

Inspection Description - SIGN SHOP

Inspection Status - Approved

Date Description Inspector Results Comments
02/17/2009 SIGN SHOP Approved IVRS - Inspection :*
02/09/2009 SIGN SHOP Denied IVRS - Inspection :
There is no access to the site.| 920*
UNIT LOCKED. NO ONE ON SITE.
CONTRACTOR TO BE ON SITE TO
PROVIDE ACCESS TO SIGNS
01/21/2009 SIGN SHOP Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED TO PROVIDE SERVICE LIGHT 210.70(C) OF NEC
2. NEED TO PROVIDE PERMANENT WALKWAY TO SIGN
AND FROM ONE END OF SIGN TO THE OTHER
MIN. 12" WIDE 600.21 OF NEC
3. INSTALL DISCONNECTING MEANS FOR SIGN WITHIN SIGHT OF SIGN OR CAPABLE OF BEING LOCKED OPEN