Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: SIGN SHOP
Permit Number - T08OT02712
Inspection Description - SIGN SHOP
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/17/2009 | SIGN SHOP | Approved | IVRS - Inspection :* | |
02/09/2009 | SIGN SHOP | Denied | IVRS - Inspection : There is no access to the site.| 920* UNIT LOCKED. NO ONE ON SITE. CONTRACTOR TO BE ON SITE TO PROVIDE ACCESS TO SIGNS |
|
01/21/2009 | SIGN SHOP | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED TO PROVIDE SERVICE LIGHT 210.70(C) OF NEC 2. NEED TO PROVIDE PERMANENT WALKWAY TO SIGN AND FROM ONE END OF SIGN TO THE OTHER MIN. 12" WIDE 600.21 OF NEC 3. INSTALL DISCONNECTING MEANS FOR SIGN WITHIN SIGHT OF SIGN OR CAPABLE OF BEING LOCKED OPEN |