Permit: T08OT02619

Parcel: 140420950

Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T08OT02619

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/25/2008 FIRE - FINAL Approved
11/07/2008 FIRE - FINAL Partial Approval APPROVED FOR A TEMPORARY C OF O ONLY UNTIL 11/24/08 AT WHICH TIME THE MULLER COMPANY IS TO HAVE COMPLIED WITH WRITTEN NOTICE FROM THE FIRE DEPT. TO MAKE CORRECTIONS TO THE SPRINKLER SYSTEM & OFFICE T.I.
11/06/2008 FIRE - FINAL Denied Replace painted sprinkler head southwest room.
Replace painted sprinkler head southeast loading dock.
Need dust collectors in wood shop to catch all sawdust, and clean up sawdust from walls and floors.
Propane bottles storage outside not allowed inside. Storage outside shall be 10 feet away from all openings into building.
Replace missing hose threads on hose cabinets.