Inspection History Details
Inspection Status: Denied
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/05/2008 | FIRE - FINAL | Denied | Not approved 12/05/08. Need 5 yr. alarm check valve inspection report. OK to approve when sprinkler co. calls and advises that chk v. inspection has been scheduled for some time in the following week. 12/8 to 12/12. |
|
| 12/05/2008 | FIRE - FINAL | Approved | Approved 12/05/08. Rep. from Simlex/Grinnell Fire Protection confirmed that check valve was scheduled for inspection/servicing on Mon. the 8th. |
|
| 12/03/2008 | FIRE - FINAL | Denied | Need up to date Fire Sprinkler inspection last on file 03/16/2001. Need up to date 5yr alarm check valve inspection done nothing on file. Post 12" inch address numbers on building per code, handout given. Open office area correct sprinkler coverage sprinkler head 8' foot off wall can n ot use the small room rule. Chain and lock main control valve in the open position. Need to install spare head box with extra heads for system. |